编码器正确的接线方法:(1)正确接线至关重要,如图1 为NPN 输出增量型E6B2-CWZ6C 的接线原理,图2 为NPN 输出增量型E6B2-CWZ6C 的实际接线,棕色线接电源正极,蓝色线接电源负极,黑色线接输入0.00,白色线接输入0.01,橙色线接输入0.04,PLC 的COM 接电源正极。https://p6-tt-ipv6.byteimg.com/img/pgc-image/d52875d2490e42a2a4f95d962a843e59~tplv-tt-shrink:640:0.imagehttps://p6-tt-ipv6.byteimg.com/img/pgc-image/13e1667372b0462da9ab17ef6121fff2~tplv-tt-shrink:640:0.image
(2)下图为PNP 输出增量型E6B2-CWZ6B 的实际接线图,棕色线接电源正极,蓝色线接电源负极,黑色线接输入0.00,白色线接输入0.01,橙色线接输入0.04,PLC 的COM 接电源负极。https://p6-tt-ipv6.byteimg.com/img/pgc-image/b78a40e731cd4ba892db6360a8bf8af9~tplv-tt-shrink:640:0.image
(3)图1 为绝对值型编码器的线与PLC 输入的点的对应图,图2 为NPN 输出绝对值型E6C3-AG5C 的实际接线图,红色线接电源正极,黑色线接电源负极,褐色线接输入0.00,橙色线接输入0.01,黄色线接输入0.02,绿色线接输入0.03,蓝色线接输入0.04,紫色线接输入0.05,灰色线接输入0.06,白色线接输入0.07,粉色线接输入0.08,PLC 的COM 接电源正极。https://p6-tt-ipv6.byteimg.com/img/pgc-image/f3e4c5bc500e4ea5b4c7c205551cbc3c~tplv-tt-shrink:640:0.image
https://p9-tt-ipv6.byteimg.com/img/pgc-image/dfed016f01ae4c8a8704ebeb4f45d3b1~tplv-tt-shrink:640:0.image
(4)下图为PNP 输出绝对值型E6C3-AG5B 的实际接线图,红色线接电源正极,黑色线接电源负极,褐色线接输入0.00,橙色线接输入0.01,黄色线接输入0.02,绿色线接输入0.03,蓝色线接输入0.04,紫色线接输入0.05,灰色线接输入0.06,白色线接输入0.07,粉色线接输入0.08,PLC 的COM 接电源负极。https://p26-tt.byteimg.com/img/pgc-image/e312e202b0ff48138684b48872ea4d5a~tplv-tt-shrink:640:0.image
(5)图1 为线驱动编码器的接线原理,图2 为实际接线图,黑色线接A0+,黑红镶边线A0-,白色线接B0+,白红镶边线接B0-, 橙色线接Z0+,橙红镶边线接Z0-,褐色线接电源+5V,蓝色线接电源0V,切勿接线错误。https://p3-tt-ipv6.byteimg.com/img/pgc-image/549c857bb619412897286317dda4c10d~tplv-tt-shrink:640:0.image